Hitachi PC-ARFG-E Installation & Operation Manual page 50

Wired remote controller
Hide thumbs Also See for PC-ARFG-E:
Table of Contents

Advertisement

SERVICE & INSTALLATION MENU
Element
Optional function
Not used
Only for KPI-E4E and
E3
KPI-X4E:
Selection of the fan for
function E2
KPI: Pre-cooling / pre-heating
period
E4
Econofresh: CO
sensor
2
Not used
Only for DX-Interface,
E5
KPI-E4E and KPI-X4E:
High ventilation after switch
ON
Period of indoor fan operation
E6
after cooling operation
stoppage
E7
Not used
Control for stop of the indoor
unit fan during heating
Thermo-OFF conditions (with
E8
remote sensor THM-R2AE
connected to the THM4
connector in the indoor unit
PCB)
E9
Not used
EA
Not used
Indoor unit fan control
Eb
during cooling Thermo-OFF
conditions
Forced Thermo-ON when
EC
stopping in cooling operation
45
PMML0565 rev.0 - 09/2021
Individual
Settings
setting
00
-
01
00
Activated for supply fan
01
Activated for exhaust fan
00
Disabled (factory setting)
01
30 minutes
02
60 minutes
O
00
Disabled (factory setting)
CO
01/02
(required setting E1=00)
00
-
01
00
Disabled (factory setting)
01
60 minutes
Disabled function
00
(factory setting)
O
01
60 minutes
02
120 minutes
00
-
01
00
Fan operation in Low speed
O
01
Fan stop in Thermo-OFF conditions.
00
-
01
00
01
-
02
Function disabled
00
(factory setting)
O
01
Low
02
Slow
Function disabled
00
(factory setting)
O
01
Enabled
Setting conditions
sensor
2
Description
Use at 00 conditions
This function selects which fan
will increase the speed
(when E2 enables this function).
This function delays unit startup
with energy recovery
This function selects the CO
2
gas sensor input for Econofresh.
Use at 00 conditions
This function forces that the unit
will operate in high speed during
60 minutes after fan start. After
this time the fan will be changed
to setting value.
This function prevents the
condensation in the unit by
keeping the fan running after the
unit operation has been turned
OFF.
Use at 00 conditions
This function stops the fan
to prevent cold draughts or
overheating.
C8 must be set to 01 to use the
E8=01 setting.
The connection of a THM- R2AE
remote temperature sensor to
the THM4 port in the indoor unit
PCB is required. The remote
sensor shall be installed in a
proper place for the correct
detection of room temperature.
(In case that automatic louver
is set, the louver will keep
operating in both Thermo- ON
and Thermo- OFF condition.)
Use at 00 conditions
Use at 00 conditions
This function decreases speed
of the indoor unit fan during
cooling Thermo-OFF, to reduce
the spread of smells and
humidity.
This function is used to force
Thermo-ON during 6 minutes
when stopping in cooling
operation.