SERVICE & INSTALLATION MENU
Element
Optional function
Not used
CC
Only for DX-Interface,
KPI-E4E and KPI-X4E:
High ventilation speed
Stop of indoor unit fan
during cooling Thermo-OFF
conditions
?
N O T E
Cd
For model RPI(L/H)-FSRE and
RCD-FSR, this function is NOT
available.
Stop of indoor unit fan
during heating Thermo-OFF
conditions
Stop of indoor unit fan
CE
during heating Thermo-OFF
conditions (with remote
control switch temperature
sensor)
Modification of louver swing
angle
Models:
RCI-FSR
RCIM-FSRE
RCD-FSR
RPC-FSR
CF
Models:
RPK-FSR(H)M
Management of indoor unit
d1
operation after a power
supply cut off - option 1
d2
Not available
43
PMML0565 rev.0 - 09/2021
Individual
Settings
setting
00
-
01
Function disabled
00
(factory setting)
01
Function enabled
Fan speed during cooling Thermo-OFF:
00
Low (factory setting)
O
Indoor unit fan is stopped during cooling
01
Thermo-OFF
Fan speed setting during heating Thermo-
00
OFF: Low (factory setting)
O
Indoor unit fan is stopped during heating
Thermo-OFF
01
(In case that automatic louver is set, the
louvers will keep operating in both Thermo-
ON and Thermo-OFF conditions)
Standard (7 steps)
00
(factory setting)
Cold draft prevention (5 steps)
01
(Cannot be set to the lower two steps;
lower 2 steps cut off)
High ceilings (5 steps)
02
(Cannot be set the upper two steps; upper
2 steps cut off)
O
Standard (7 steps)
00
(5 steps for cooling / dry mode)
Cold draft prevention
(5 steps for heating and fan only)
01
(Cannot be set to the lower two steps,
lower 2 steps cut off)
02
Not used
Function disabled
00
(factory setting)
O
01
Function enabled
"- -" permanent –
Setting conditions
(4)
(5)
(5)
Description
Use at 00 conditions
This function sets the unit to run
in high fan speed regardless
the setting from remote control
switch.
The operation of the indoor unit
fan is stopped in cooling Thermo-
OFF conditions when using the
additional remote temperature
sensor
THM-R2AE (connected to THM4)
or the PC-ARFG-E temperature
sensor.
C8 must be set to 01 to use the
Cd=01 setting.
The indoor unit uses the
PC-ARFG-E temperature sensor
to monitor the room temperature
when the fan is stopped
(heating Thermo-OFF fan stop
sequence).
C8 must be set to 01 to use the
CE=01 setting.
Control by remote temperature
sensor connected to THM4 is
not permitted (use E8 function in
that case).
This function adjusts the angle
of the air outlet louver.
(Changes to the setting of this
function are applied after turning
the power supply off and on
again, or after the automatic
louver has made a full cycle in
automatic mode).
When power supply is restored,
the indoor units controlled by
the wired remote control switch
are turned on regardless of their
ON/OFF status at the time of the
last power cut off.