SERVICE & INSTALLATION MENU
Element
Optional function
Cancellation of forced
compressor operation for at
least 3 minutes
C7
Only for KPI-E4E and
KPI-X4E
CO
sensor enabled
2
Control by the temperature
sensor of the remote control
switch.
(2)
?
N O T E
The remote control switch
shall be installed in a proper
place for the correct detection
of room temperature by its
temperature sensor.
Control sensor when a
remote sensor is connected
to the THM4 connector in the
indoor unit PCB.
(3)
?
N O T E
The remote sensor shall be
installed in a proper place for
the correct detection of room
temperature.
C8
(1)
Model
RPF(I)-FSN2E
Control sensor when a
remote sensor is connected
to the THM4 connector in the
indoor unit PCB.
(3)
?
N O T E
The remote sensor shall be
installed in a proper place for
the correct detection of room
temperature.
All indoor units except
RPF(I)-FSN2E
C9
Not available
CA
Not available
Selection of forced stoppage
Cb
logic
42
PMML0565 rev.0 - 09/2021
Individual
Settings
setting
Function disabled
00
(factory setting)
Function enabled
01
(Compressor operation during 3 minutes
is no longer forced)
O
Sensor non enabled
00
(factory setting)
01
Sensor enabled/activated
Control by the air inlet sensor of indoor
00
units (factory setting)
Control by the temperature sensor of the
01
remote control switch
O
Control by the average value of the
air inlet sensor of indoor units and the
temperature sensor of the remote control
02
switch
(Air inlet + Remote control switch)/2
When a remote sensor is connected to
THM4, this remote sensor is used as
00, 01, 02
control sensor, whichever the setting for
C8 (factory setting C8=00)
Air temperature control using the average
O
value of the air inlet thermistor and the
remote sensor
00, 02
(factory setting C8=00)
(Air inlet + Remote sensor)/2
Air temperature control using the remote
01
sensor
–
"- -" permanent –
–
"- -" permanent –
Forced stoppage input: A contact,
00
normally open contact (factory setting)
X
Forced stoppage input: B contact,
01
normally closed contact
Setting conditions
Description
This function is available
depending on the setting of
function b3.
Via 7-segments display set the
option Ct (00: ON/OFF Sensor
(Default); 01: 4-20mA 02: 0-10V)
This function specifies the
temperature sensor to be used
as control sensor by the indoor
unit.
–
–
This function determines the
logic operation for the forced
stoppage contacts.