348 Technical data
Brake resistor connection data for frames R1...R3
Short-circuit protection
(IEC/EN 61800-5-1, IEC 61439-
1)
Auxiliary circuit power consumption
Efficiency
Note:
1.
Radiated and conducted emissions are according to
category C2 with an internal EMC filter. The internal
EMC filter must be connected.
2.
Categories C1 and C2 meet requirements for connecting
equipment to the public low-voltage networks.
3.
Not applicable to 600 V ratings.
4.
Radiated and conducted emissions are according to
category C3 with an internal EMC filter. The internal
EMC filter must be connected.
The brake resistor output is conditionally short-circuit proof
by IEC/EN 61800-5-1. Rated conditional short-circuit current
as defined in IEC 61439-1.
Maximum external power supply:
Frames R1...R5: 25 W, 1.04 A at 24 V AC/DC (with option modules
CMOD-01, CMOD-02)
Frames R6...R9: 36 W, 1.50 A at 24 V AC/DC (as standard, termin-
als 40...41)
Approximately 98% at nominal power level. The efficiency is not
calculated according to IEC 61800-9-2.