250 Maintenance

Fans

See
Maintenance intervals (page 243)
for the fan replacement interval in average
operation conditions.
Parameter 05.04 Fan on-time counter indicates the running time of the cooling
fan. Reset the counter after a fan replacement. See the firmware manual.
In a speed-controlled fan, the speed of the fan matches the cooling needs. This
increases the life span of the fan.
Main fans are speed controlled. When the drive is stopped, the main fan runs at
low speed until the drive cools down. IP21 (UL Type 1) frames R5...R9 and all IP55
(UL Type 12) frames have auxiliary fans that are not speed controlled and run all
the time when the control unit is powered.
Replacement fans are available from the manufacturer. Do not use other than
specified spare parts.