CHAPTER 7: CONNECTING FIELD WIRING TO THE D20E MODULE

Form C control outputs

Raise/Lower control outputs

DPST control outputs

D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
The Form C control output is a dry contact output. The control uses two complementary
outputs (see Figure 20):
One normally open, and
One normally closed.
There are 32 Form C control outputs that can be configured on the D20E-K.
Figure 20: Form C outputs
A Raise/Lower control output uses either a raise relay or a lower relay to increment or
decrement a value (i.e., tap changer).
Each Raise/Lower set uses two control output select relays (see Figure 21):
One for the raise and
One for the lower.
This supports 16 Raise/Lower control outputs using 32 select relays on the D20E-K.
Figure 21: Raise/Lower outputs
Each Double Pole Single Throw (DPST) output only requires one relay to be energized to
perform a control output operation. Both supply polarity leads are switched (see Figure 22).
Figure 22: DPST outputs
DPST outputs are shown as DO(+/‒) in Table 23. 32 single DPST outputs are available on the
D20E-K.
The wiring connected to terminal block TB2 must not have exposed accessible
conductors.
The wire and cable connected must have at least a +80
C temperature rating.
°