Control Output Point Quality Flag; Control Output Point Configuration Settings - GE Multilin D20E Installation And Maintenance Manual

Ethernet i/o module
Table of Contents

Advertisement

Control output point quality flag

Control output point configuration settings

70
A digital control point includes the quality flags listed in Table 18.
Table 18: Digital control point quality flags
Quality flag
Description
On-line
This bit indicates an output's online/offline state.
Restart
This bit indicates if the device (point) has restarted, but has not been
initialized yet.
Communication Lost
This bit is set when this point is off-line,
Remote Forced
This bit is set when the point is remote forced;
Local Forced
This bit is set when the point is locally forced.
Chatter Filer
This bit is set when the chatter file is active for this point (need confirm).
Reference Check
This bit is set when the analog input reference is not set (may not be
needed).
The control/digital output is the control point in D20E-K and D20E-C modules.
Table 19 lists the Control/Digital Output Point configuration settings and recommended
setting values.
Table 19: Control/Digital output points configuration settings
Setting
Descriptions
General settings
Reference
Specify a text string that combines the bay
Name
name, group name, and provider name from
the General tab.
Bay Name
Specify the name of the bay to which the
digital output belongs.
Group Name
Specify a unique name used in conjunction
with the below Point Description setting when
referencing the Provider Application Digital
Point information.
The Group Name is used by the HMI for
trending and event querying; therefore, using a
label associated with the substation topology
is recommended.
Point Name
Specify the name of the point.
The Point Name should be unique within the
bay and group to which it belongs.
Point
Specify a descriptive label for the digital output
Description
point.
This setting is used in the HMI Application Point
Status Viewer and Event Recorder.
Value Type
Specify the data type the Provider application
uses when storing the digital output in the
database.
Initial Value
Specify the initial counter value that appears in
the database during initialization.
Command
Specify the digital output type used to
Type
command the remote device.
GE INFORMATION
CHAPTER 3: CONFIGURING THE D20E FIRMWARE
Range
0 to 64 characters
0 to 128 characters
Single Point
Double Point
Open
Close
Trip/Close
Regulating step
Reset
Freeze
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
Default
Trip/
Close