Counter Points - GE Multilin D20E Installation And Maintenance Manual

Ethernet i/o module
Table of Contents

Advertisement

Counter points

Configure counter
points
Counter type
Dual point counter
60
The Digital Input points in the D20E-S and D20E-C modules can be configured as counter
type points. When a digital input is configured as a counter point, each digital status
change event is accumulated and reported as a counter value.
A Digital Input and a Counter cannot be assigned to the same contact.
To configure a counter point:
1.
Remove a Digital Input from the point list.
2.
Add the Counter to the point list.
If a Digital Input and Counter are configured to share the same contact, an error message
appears and a sync with the D20E is not allowed.
A Digital Input point can be configured with the counter types listed in Table 8.
Table 8: Counter type descriptions
Counter type
Description
Binary
Single input counter that accumulates a specified polarity transition or state
change.
Binary Frozen
Binary counter in conjunction with a protocol freeze command.
Form C
This is a two-input counter, the same as a standard KYZ counter. When any
complimentary state change occurs simultaneously on the two inputs, the
counter increases in value on the specified high or low polarity transition.
Form C Frozen
Form C counter in conjunction with a protocol freeze command.
Dual Point
This is a two-input switch or breaker operation counter. See figure for
functionality.
Dual Point Frozen
DP counter in conjunction with a protocol freeze command.
The states of a dual point counter are listed in Table 9.
Table 9: Dual point counter - states
Number of possible indicator states
1
2
3
4
Figure 10 shows the indicator states triggered by Point 1 and Point 2. The first transition is
from Point 1, then the opposite transition from Point 2, and so on.
Figure 10: Dual point counter - state changes
Point 1
Point 2
Counts
1
GE INFORMATION
CHAPTER 3: CONFIGURING THE D20E FIRMWARE
State of point 1
1
0
1
0
2
D20E ETHERNET I/O MODULE INSTRUCTION MANUAL
State of point 2
0
1
1
0
3
4

Advertisement

Table of Contents
loading