Step 3 Open the corresponding maintenance door, and apply sealant to the joint between
the air vent and flexible connection inside the unit.
----End
4.3.6 Removing the Transport Fasteners and Protective Covers
Procedure
Step 1 Open the maintenance door. Loosen the three bolts on the compressor transport
fasteners using a 13# solid wrench.
Figure 4-12 Removing the transport fasteners from the compressor
Step 2 Remove the transport fasteners.
Step 3 Tighten the bolts securing the compressor using a torque wrench.
Step 4 Open the maintenance door, and take out the desiccant bags from the device.
Figure 4-13 Position of the desiccants
Issue 04 (2022-06-30)
NO TE
● Do not remove the bolts directly.
● Put away the removed transport fasteners so that you can reinstall them if the indoor
unit is to be transported again in the container scenario.
Copyright © Huawei Technologies Co., Ltd.
4 System Installation
47