6.5 Startup

Context
On the main screen of the display module, there are Start and Shutdown buttons
for controlling the startup and shutdown of the units.
Prerequisites
Issue 04 (2022-06-30)
Check that the number of units in the topology is the same as the actual
number of units.
If yes, go to 2.
If no, check the cable connection and the teamwork settings.
Check that the number of running units in the topology is the same as the
actual number of units.
If yes, go to 3.
If no, check the cable connection and the teamwork settings.
Check that the number of standby units in the topology is the same as the
actual number of units.
If yes, go to 4.
If no, check the cable connection and the teamwork settings.
Check that the number of online units in the topology is the same as the
actual number of units.
If yes, the check is complete.
If no, check the cable connection and the teamwork settings.
If the unit is powered on again after a power failure, the unit automatically
restores to the original startup/shutdown state before the power failure.
Hardware ports are reserved on the display module to control the status of
remote dry contacts or remote startup and shutdown signals. The status of
remote dry contacts and remote startup and shutdown signals is started by
default.
Starting a unit over the screen or NMS is valid only when the status of remote
dry contacts or remote start/shutdown signal is started.
If you choose Settings > System Settings > System Control and set Require
password to start or shutdown onsite to Yes, a password is required for
startup or shutdown; if you set Require password to start or shutdown
onsite to No, no password is required for startup or shutdown verification.
Download the Service Expert app from the app store. The app can only run
on Android currently. You must apply for the permission to use the app after
downloading it.
Before starting the unit, check whether there are oil stains on a refrigerant
pipe or a large number of bubbles in the sight glass. If so, the pipe leaks. You
need to rectify the leakage and refill refrigerant onsite to ensure that the unit
runs properly.
Copyright © Huawei Technologies Co., Ltd.
6 Power-On and Commissioning
96