Huawei NetCol8000-A013 User Manual page 83

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Setting
Item
Unit
Address
Enable
Teamwork
Resistor
Units in
Group
Active
Units in
Group
Issue 04 (2022-11-25)
Description
Indicates a smart
cooling product
address in a
teamwork control
group. The address
can be set to 1 for
only one unit in
each group, and
must be unique for
all other units in the
group.
Indicates the build-
out resistor status of
each smart cooling
product in a
teamwork group.
Indicates the
number of smart
cooling products in a
group. The value is
an integer ranging
from 1 to 32.
Indicates the
number of running
units in a group. The
value is an integer
ranging from 1 to
the number of units
in a group.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Power-On Commissioning
Setting Principle
Set the planned unit
address.
● Set this
parameter to No
for non-
teamwork
scenarios.
● For teamwork
scenarios, set this
parameter to Yes
for the first and
last smart cooling
products in a
teamwork group,
and set it to No
for other smart
cooling products.
Set this parameter
to the number of
smart cooling
products in a group.
Assign the address 1
to the master unit,
and assign addresses
starting from 2
consecutively to all
running units in a
group. Remaining
units will be
regarded as standby
units.
Default Value
--
--
3
2
76

Advertisement

Table of Contents
loading

Table of Contents