Huawei NetCol8000-A013 User Manual page 103

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Alarm
Alarm Name
ID
214
Comp Drive DC
Overvolt Alarm
215
Comp Drive DC
Undervolt Alarm
Issue 04 (2022-11-25)
System
Action
The
compressor
shuts down.
The
compressor
shuts down.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 System Operation and Maintenance
Possible Causes
The input voltage of
the compressor drive
board is higher than
the preset threshold.
The input voltage of
the compressor drive
board is lower than the
preset threshold.
Solution
1. Check whether the
input power is
within the normal
range.
2. Use an oscilloscope
to check whether
the waveform of the
power grid is within
the normal range.
3. Replace the
compressor drive
board if it is faulty.
1. Check whether the
input power is
within the normal
range.
2. Use an oscilloscope
to check whether
the waveform of the
power grid is within
the normal range.
3. Replace the
compressor drive
board if it is faulty.
96

Advertisement

Table of Contents
loading

Table of Contents