Figure 2-8 Controller appearance
Teamwork Control
The controller has powerful teamwork control functions. Each smart cooling
product is equipped with a controller. Based on the site requirements, a maximum
of 32 smart cooling products in one area can be grouped for teamwork control,
with smart cooling product 1 as the master to implement central control and
management. Teamwork control functions include:

2.2.2.4 Monitoring System

The monitoring system provides logic control, control demand delivering, alarm
reporting, data storage, user right management, and teamwork control functions.
Issue 04 (2022-11-25)
When a smart cooling product in the group is faulty, the backup smart
cooling product starts to operate automatically to improve the reliability of
the smart cooling product system.
Each smart cooling product enters the active mode one by one periodically,
balancing the service life of each smart cooling product.
On-demand operation: The number of operating smart cooling products
varies with thermal loads in the equipment room to save energy.
A mechanism is adopted to prevent the smart cooling products in the same
equipment room from operating in opposite status (such as humidification
and dehumidification), in order to save energy.
Copyright © Huawei Digital Power Technologies Co., Ltd.