Demounting; Electric Connection; Procedure To Connect The Lines To X1S1/X1S2; Line Lengths And Cross-Sections - Bosch Rexroth IndraControl VAC 01 Operating Instructions Manual

Y-repeater
Table of Contents

Advertisement

DOK-SUPPL*-VAC*01*****-IT04-EN-P
IndraControlVAC 01 Y-Repeater
10.5

Demounting

10.6

Electric connection

10.6.1

Procedure to connect the lines to X1S1/X1S2

10.6.2

Line lengths and cross-sections

Use two M5 screws to attach the Y-repeater to the rear panel.
2. Fixing the cables
Unfixed cables are not permitted. Therefore, an appropriate fixing (e. g.
installation in a cable channel) and a strain relief of the cables is re‐
quired.
Preparing the demounting
1. Demounting the Y-repeater from the rear panel
Remove the both M5 screws used to attach the Y-repeater to the rear
panel.
Connect the lines as described in the following:
1. Strip the lines to a length of 9 mm.
2. Loosen the spring by pressing it using the screwdriver ①.
3. Put the line into the terminal point ②.
4. Fix the line by removing the screwdriver.
Fig. 10-4:
Connecting the lines at X1S1 or X1S2
Bosch Rexroth recommends a 0.4 mm x 2.5 mm x 80 mm screw‐
driver.
Connection
Cable length
24 V +
30 m max.
24 V -
SEL +
100 m max.
ESM +
SEL/ESM* -
Functional earth
1 m max.
Only the Y-repeater VAC01.1S-YD1-TCES
Tab. 10-1:
Cable lengths and cross-sections for the plugs X1S1 or X1S2
Bosch Rexroth AG
Mounting, demounting and electric installation
1 1
2
Conductor cross-sections
1.5 mm
2
0.2 mm
2
24-16)
6.0 mm
2
27/53
(AWG 16)
to 1.5 mm
2
(AWG
(AWG 9)

Advertisement