Error With Modbus Tcp Connection; Error With Firmware Update - Siemens Sentron 7KN POWERCENTER 1000 Manual

Circuit protection devices with communication and measuring function
Hide thumbs Also See for Sentron 7KN POWERCENTER 1000:
Table of Contents

Advertisement

9.2

Error with Modbus TCP connection

Fault description
Devices not reachable
Data point provides incorrect value
Parameters cannot be modified
9.3

Error with firmware update

Fault description
Update not possible
Update runs into a timeout
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01
Solutions
Check power supply (communication only possible if the device is supplied
with power. If necessary, the device has tripped)
Check the correct device address
Check the correct register
Check the correct device address and register of the desired device (each
terminal device does not support each data point)
Check whether the start address of the register has been decremented by -
1 for readout
Check the correct function code
Check the value range
Solutions
Check the power supply
Check the error-free communication
Check the correct firmware version (this must be higher than the current
one)
Check the correct device type
Restart firmware update
Restart update
9.2 Error with Modbus TCP connection
FAQs
85