Management System Cable Connection; Connecting Cabinet Electronic Clasp Lock Cables - Huawei FusionModule500 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Figure 4-113 Connecting communications cables between lithium batteries and
the UPS
----End

4.3.4 Management System Cable Connection

4.3.4.1 Connecting Cabinet Electronic Clasp Lock Cables

Prerequisites
The cabinet electronic clasp locks have been installed.
Procedure
Step 1 Install cabinet electronic clasp lock cables according to the cabinet electronic clasp
lock layout.
Issue 02 (2020-12-25)
NO TE
Connect one end of a network cable to the RS485_IN port on the electronic clasp lock on
the front door of the cabinet, and connect the other end to the COM3 port on the ECC800-
Pro. Connect one end of another network cable to the OUT port on the electronic clasp lock
on the front door of the cabinet, and connect the other end of the network cable to the
RS485_IN port on the electronic clasp lock on the rear door of the cabinet.
Copyright © Huawei Technologies Co., Ltd.
4 Installation Guide