4.2.6.5 Routing the Cable to a WLDS900 Water Sensor

If the water sensor is required, perform the following steps to install it.
Context
Figure 4-52 Water sensor
(1) Water detector
(4) Conversion cable end B,
connected to the water
detection cable
Do not contact the water detection cable to metal, for this action will cause a
false alarm. Take protective measures when routing the water detection cable.
Issue 02 (2020-12-25)
The water sensor is composed of the water detection cable (BOM number:
33010445), water detector (BOM number: 33010352), and conversion cable
(packed with the water detector).
The water detector is bound to the 5th U position on the left mounting bar of
the cabinet rear door.
The water detection cable and water detector are interconnected using the
conversion cable.
A single water detection cable is 5 meters long. If a longer cable is required,
connect the male connector of a water detection cable to the female
connector of another. One water detector can be connected to a maximum of
nine water detection cables.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
(2) Conversion cable end A,
connected to the water
detector
(5) Water detection cable end
A, connected to the conversion
cable
4 Installation Guide
(3) Conversion cable
(6) Water detection cable
110