Action
"Access"
Scroll to menu S5.
"A"
"A"
Rev: 1

Clear weekly average (H8/S5)

If a sensor (analog smoke detector) is replaced without having
generated SERVICE signal, its week average sensor value has to be
set to the default value otherwise the new / clean sensor will inherit
the old sensor's value. It is possible to clear the week average sensor
value for each sensor individually.
NOTE! Authorised service personnel only, must do the reset to
default value. Used incorrectly it can cause nuisance fire alarms.
The first week average sensor value (after clearing) will be calculated
within one hour and after that each week.
Text in display
Clear weekly average
Enter technical number to clear: 000000
Clear weekly average
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT?
ACCEPT?
ACCEPT?
124
Comments
According to chapter
"Access code for
maintenance", see page
119.
S5
Write the wanted techn.
no. and/or press "A" to
accept.
Scroll or press "Return" to
return to menu H8. Scroll
S5
or press "Return" to log
off.