Disconnect Loop (H8/S2) - Panasonic EBL512 Operating Instructions Manual

Fire alarm system ebl512 v2.3.x
Hide thumbs Also See for EBL512:
Table of Contents

Advertisement

Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
30.3
Action
"Access"
Scroll to menu S2.
"A"
"A"
Depending on the
chosen type, 0, 1, 2 or
3, the following will be
shown:
"A"
"Return"
Rev: 1

Disconnect loop (H8/S2)

Before physical connection / disconnection of loop units, etc. the loop
(or zone line) shall be disconnected (disabled), i.e. there will be no
voltage on the "loop" to avoid damage on the units and the c.i.e.
BS4 loop require an Autronica interface board 1584 in the control
unit. DET8 "loop" (zone line) requires an 8 zones expansion board
1580 in the control unit.
Text in display
Disconnect loop
Disconnect type: 0 (0=COM, 1=BS4,)
2=DET8, 3=Loop Unit)
Disconnect COM-Loop: 0, CU: 00
Disconnect BS4-Loop: 0, Board: 0, CU: 00
Disconnect DET8-input: 0, Board: 0,
CU: 00
Disconnect input technical no.: 000000
Disconnect type: 0 (0=COM, 1=BS4,)
2=DET8, 3=Loop Unit)
Disconnect loop
90
Only valid for input 0 as a zone line input (Z), i.e. trigger cond. no. 19.
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
121
Comments
According to chapter
"Access code for
maintenance", see page
119.
S2
Press:
"0"=COM loop
"1"=BS4 loop
"2"=Expansion board 1580
"3"=Addr. zone interface
2226 / 2335 / 2821 or
90
3361
(MIO).
Press "A" to accept.
Write the required
numbers. Press "A" to
accept.
90
LED "Disablements"
indicates disconnected
loops, etc. Continue to
disconnect or press
"Return" to menu S2.
Scroll or press "Return" to
return to menu H8. Scroll
S2
or press "Return" to log
off.