Huawei FusionCol8000-E240 User Manual page 160

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 8-13 Removing the T/H sensor
Step 4 Remove the outdoor air intake T/H sensor. Remove the screws from the sheet
metal fastener of the T/H sensor.
Figure 8-14 Removing the T/H sensor
Step 5 Disconnect the cable from the T/H sensor.
Step 6 Slide and remove the T/H sensor.
Step 7 Install the new T/H sensor and reconnect the cable.
Before installing the new T/H sensor, check that its DIP switch settings are
consistent with the DIP switch settings of the old T/H sensor.
Step 8 Power on the device and tap Start on the home screen. Ensure that the device is
running properly without generating alarms.
----End