Huawei FusionCol8000-E240 User Manual page 117

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Paramete
r
Cold aisle
temperatu
re and
humidity
sharing
Hot aisle
temperatu
re and
humidity
sharing
Differentia
l pressure
sharing
Step 3 Perform
products in the group.
Step 4 On the home screen of any teamwork controlled smart cooling product, tap
If the teamwork control succeeds, the teamwork topology of the smart cooling
product in the group is displayed.
Issue 01 (2021-01-30)
Description
This parameter can be
enabled only when at least
two smart cooling products
in the group are configured
with cold aisle T/H sensors.
When this parameter is
enabled, the smart cooling
product, which is not
configured with the cold
aisle T/H sensor in the
group, is logically controlled
by using the acquired value
of the configured cold aisle
T/H sensor.
This parameter can be
enabled only when at least
two smart cooling products
in the group are configured
with hot aisle T/H sensors.
When this parameter is
enabled, the smart cooling
product, which is not
configured with the hot
aisle T/H sensor in the
group, is logically controlled
by using the acquired value
of the configured hot aisle
T/H sensor.
When this parameter is
enabled, the smart cooling
product, which is not
configured with the
differential pressure sensor
in the group, is logically
controlled by using the
acquired value of the
configured differential
pressure sensor.
Step 1
and
Step 2
to configure teamwork control for all smart cooling
Copyright © Huawei Technologies Co., Ltd.
6 Power-On Commissioning
Configuration Rule
This parameter can be
enabled when at least
two smart cooling
products in the group
are configured with
cold aisle T/H sensors.
This parameter can be
enabled when at least
two smart cooling
products in the group
are configured with
hot aisle T/H sensors.
This parameter can be
enabled when there
are at least two smart
cooling products in
the group are
configured with
differential pressure
sensors.
Default
Value
Disable
Disable
Disable
.
108