Control With Graphic Display - Siemens SIPROTEC 5 Manual

V8.30 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Operation in the Operating State
8.9 Control System on Site
Proceed as follows for devices without a key switch:
Select the menu item Commands in the main menu.
²
Go to the menu item Switching mode.
²
Select Interlocked or Non-interlocked and confirm with Ok.
²
You can set this switchover after entering the confirmation ID.
²

Control with Graphic Display

8.9.5
Devices with a graphic display can depict a single-line diagram of the field in the control display, see
Figure
8-63. You can create the control display with the display editor of DIGSI 5. The display becomes active
directly after activation. You can reach the display at any time by pressing the yellow <Ctrl> key.
[scabzstb-280211-01.tif, 1, en_US]
Figure 8-63
Selecting Switching Device
From this control display you can select the individual switching devices using the navigation keys. After the
position has been switched, the feedback is shown directly in the control display. A separate default display
(single line without control capability) is not present but can be created.
Refer to the notes in chapter
Initiating command
Select the switching device to be controlled using the navigation keys.
Then enter the new target position ON or OFF with the corresponding control key (green <I> for ON, red
<O> for OFF).
Confirm the query with the softkey marked Ok in the display.
If the switching operation is permissible, it is executed, otherwise you receive a notification about the cause of
rejection.
204
Control Display
5.3 Displays for Indication and
Control.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020

Advertisement

Table of Contents
loading

Table of Contents