Operation in the Operating State
8.4 Indications
You can find more details on the topic of LED reset in chapter
Device

Stored Indications in the SIPROTEC 5 Device

8.4.7
In your SIPROTEC 5 device, you can also configure indications as stored. This type of configuration can be
used for LEDs as well as for output contacts. The configured output (LED or contact) is activated until it is
acknowledged. Acknowledgment occurs via:
On-site operation panel
DIGSI 5
Binary input
Protocol of substation automation technology
Configuration of Stored Indications with DIGSI 5
In the Information Routing of each device set up in DIGSI 5, you can route binary signals, among others, to
LEDs and output contacts.
To do this, proceed in the project tree to:
Project → Device → Information routing
Right-click the routing field of your binary indication in the desired LED or binary output column in the
routing range of the targets.
You are offered the following options:
Table 8-5
Routing Options
H
(active)
L
(active)
V
(unlatched)
G
(latched)
154
Overview of Routing Options
LEDs
BOs
BIs
X
X
X
X
X
X
8.4.7 Stored Indications in the SIPROTEC 5
Description
The signal is routed as active with voltage.
The signal is routed as active without voltage.
The signal is routed as unlatched. Activation and reset of
the output (LED, BO) occurs automatically via the binary-
signal value.
The binary signal is latched when the output (LED) is acti-
vated. To reset, a targeted confirmation must occur.
C53000-G5040-C003-C, Edition 08.2020
SIPROTEC 5, Operation, Manual