Figure 5-4
A switch according to ISO 13850, positive opening according to IEC 60947-5-1 or a certified
safety control must be used as actuating element.
5.2.2.2

Use of the K82 option with Control Unit CU320-2

In conjunction with option K90 or K95 (CU320-2 DP or CU320-2 PN), terminal -X41:10 is
already connected inside the cabinet with digital input DI 7 of the CU320-2.
These interconnections have to be taken into account when Safety function parameters are
assigned.
Safety Integrated
Function Manual, 08/2023, A5E03264275A
5.2 Control of "STO" and "SS1" via terminal module for option K82
Circuit Terminal Module for option K82
Controlling the safety functions
45