Fitting the Devices
3.2 Surface-Mounted Devices with Integrated On-Site Operation Panel
[dw_drilling non modular surface mounting with several consoles, 1, en_US]
Figure 3-26
*
The 149 mm are valid if several mounted consoles are to be mounted next to each other.

Fitting Devices

3.2.1
Preparations
NOTE
i
i
You must mount the devices vertically.
NOTE
i
i
Siemens recommends detaching the on-site operation panels before fitting the device. Fit the on-site oper-
ation panels after completing wiring and checks.
NOTE
i
i
Use a PZ2-size Phillips screwdriver.
For each module, you need 4 fastening screws with a shank diameter of 6 mm (0.16 in).
!
DANGER
Danger due to device being improperly screw-fastened
Incomplete and careless screw fitting results in death, severe injury, or considerable material
damage!
Ensure that screw-fastening is complete at all intended bolting points. Tighten the screws to a torque
²
of 1.2 Nm.
Produce the holes as shown in the drilling plan.
²
58
Drilling Pattern of a Non-Modular Surface-Mounted Device – Several Consoles