Charging parameters
Parameter
End-of-charge voltage
Charge current
● End-of-charge voltage
The end-of-charge voltage is the maximum voltage up to which the battery is charged.
● Charge current
The battery is not charged with more than the selected charge current. The
manufacturer's details for the permitted charge current of the battery must be observed.
Note
When UPS1100 battery modules are used, both parameters are automatically set, and do
not have to be defined.
The following, device-dependent maximum values apply:
– SITOP UPS1600 10 A: Maximum permissible charge current 3,000 mA
– SITOP UPS1600 20 A: Maximum permissible charge current 4,000 mA
– SITOP UPS1600 40 A: Maximum permissible charge current 5,000 mA
Reset parameters
Parameter
Reset time
Here, you define the interrupt duration for the "Interrupt output voltage" function (reset after
buffering)
Buffering parameters (2)
Parameter
Expected buffer current
Load current, which is expected at the device output during buffer operation. If a value of 0 A
is entered, then for this parameter, the average value of the actual load current measured at
the output over the last 10 min is assumed. The value of this parameter is used when
calculating the remaining buffer time. The entered value may not exceed the rated device
current.
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76
Derating for T
> 40 °C or U
u
Derating for T
> 40 °C or U
u
Derating for T
> 40 °C or U
u
Value range
1 ... 120 s
Value range
0 ... 40 A
Value range
24 ... 30 V
1 ... 4,000 mA
< 24 V: 2,000 mA
in
< 24 V: 3,000 mA
in
< 24 V: 3,000 mA
in
Default setting
5 s
Default setting
0 A
Engineering and remote access
3.4 SIMATIC STEP 7
Default setting
26 V
800 mA
73