Installation

Note
When installing the devices, the relevant country-specific regulations must be complied with.
The 24 V supply voltage must be SELV in accordance with EN60950-1 and EN50178.
Only qualified personnel are allowed to install the device/system and set it into operation.
The connections must not be attached or detached during operation.
Note
for SITOP UPS1100
The self-discharge rate of the batteries is approx. 3%/month for a temperature of 20° C. This
value is temperature dependent and becomes more unfavorable for an increasing
temperature, and more favorable for a decreasing temperature.
The fuses should only be inserted in the fuse holder when commissioning the device.
SITOP UPS1100 1.2 Ah is only recommended in conjunction with SITOP UPS1600 10 A.
SITOP UPS1100 2.5 Ah, 3.2 Ah and 5 Ah are only recommended in conjunction with
SITOP UPS1600 10 A and 20 A.
When using battery modules without Energy Storage Link, it must be ensured that the
selected batteries match the data of the UPS1600 (static and dynamic load current, charge
current).
SITOP UPS1600 / UPS1100
Manual, 04.2016, A5E37775406-6-76