Technical data
8.1 Input
8.1.2

SITOP UPS1100

Charge current: For one connected battery module the max. charge current is 0.3C A, for
several battery modules connected in parallel, the charge current is 0.3C A multiplied by the
number of batteries connected in parallel, however, limited by the maximum permissible
charge current of the UPS1600 (see Chapter 8.2.1).
Recommended end-of-charge voltage (standby use), dependent on the battery temperature
6EP4131-0GB00- ... (1.2 Ah)
6EP4133-0GB00- ... (3.2 Ah)
6EP4134-0GB00- ... (7 Ah)
6EP4135-0GB00- ... (12 Ah)
at -10 C
-
at 0 C
-
at 10 C
27.8 V
at 20 C
27.3 V
at 30 C
26.8 V
at 40 C
26.6 V
at 50 C
-
at 60 C
-
See also
SITOP UPS1600 (Page 157)
Output (Page 157)
156
6EP4132-0GB00- ... (2.5 Ah)
29.0 V
28.6 V
28.3 V
27.9 V
27.5 V
27.2 V
26.8 V
26.4 V
6EP4133-0JB00- ... (5 Ah)
29.28 V
29.52 V
29.16 V
28.8 V
28.8 V
28.8 V
27.8 V
-