Troubleshooting
Error
Extended
Maintenance
Type
Error Type
256
20
256
21
256
22
256
23
256
24
256
25
256
26
257
1
257
2
257
3
257
4
257
5
257
6
257
7
257
12
257
13
257
15
257
16
257
17
257
18
257
19
257
20
257
21
136
Alarm Text
MR
Write error
MR
Read error
MR
Wrong device ID
MR
Corrupt data record
MR
Wrong update
MR
Too much data
D
Device failure
MD
Buffer mode not possible.
MD
Device temperature critical
(too high)
MD
Device temperature critical
(too low)
D
High-resistance connection
to battery.
D
Connection to battery inter-
rupted.
MD
Unknown battery
MR
Overcurrent
MR
Reset executed.
MR
Battery test
MR
Input voltage is too high
MD
Surplus battery
D
DC UPS parameters corrupt. DC UPS parameters corrupt - attempt to update the
D
Device overtemperature
MR
Battery SoH test
MR
Low voltage mode
MR
Buffering
Help Text
Cannot write to flash - hardware may be defective.
Unable to read EEPROM. Device is defective.
An attempt was made to update the software with
an update file that is not suitable for the DC PS.
Error during software update - try to update the
software again.
An attempt was made to update the software with
an invalid update file. The update file is probably too
old.
An entry in the software update cannot contain more
than 32 bytes of reference data.
Device failure
Buffer mode is not possible - check settings, ca-
bling, fuse, and battery voltages
Device temperature is very high! Ensure adequate
cooling or disconnect unnecessary loads.
Device temperature is very low! Ensure a higher
ambient temperature.
High-resistance connection to battery - check the
battery power cables.
Connection to battery interrupted - check connection
and fuse.
Data from the battery cannot be read correctly.
Battery is defective or not supported by SIEMENS.
Output current of DC UPS is too high. Output is
switched off for 20 s The output is switched on
again after 20 s.
Input voltage at DC UPS was OK again before the
buffer time expired. Connected devices are reset by
switching off the DC UPS outputs for the configured
time.
Battery "State of Health" tests (SoH) are performed.
The output of the DC UPS is connected to the bat-
tery in order to determine the actual battery capaci-
ty.
Input voltage exceeds 30 V. DC UPS is not opera-
tional.
More than 6 batteries are connected. Connect a
maximum of 6 batteries to the Energy Storage Link.
software.
Output and battery charging is switched off to pre-
vent damage to the device.
Battery "State of Health" tests (SoH) are performed.
Input voltage of DC UPS is too low. DC UPS is not
ready for buffering.
Device is in the buffer mode.
Manual, 04.2016, A5E37775406-6-76
SITOP UPS1600 / UPS1100