H/C Changeover Relay And Fault Messages - Siemens Synco 700 Series Basic Documentation

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Configuration
Settings
Heating/cooling
changeover relay
Configuration
Current contact position
Fault status messages
H/C changeover signal
failure
Fault status message
5801
> 1 H/C changeover signal
Fault status message
5802
Building Technologies
HVAC Products
Main menu > Commissioning > Extra configuration > Heating/cooling changeover
Operating line
Heating/cooling based on calendar
Main menu > Commissioning > Settings > Heating/cooling changeover
Operating line
Start date, heating
Start date, cooling
The changeover occurs on the "Start date, heating" or "Start date, cooling".
9.2.4

H/C changeover relay and fault messages

If, instead of being transmitted over the bus, the H/C changeover signal is to be
made available at a relay output e.g. for switch control of a valve or for forwarding
to a non-communicating device, the H/C changeover relay can be configured
accordingly. See the notes on connecting the primary controller to the changeover
valve.
Main menu > Commissioning > Extra configuration > Heating/cooling changeover
Operating line
Heating/cooling changeover relay
The current contact position (status) of the changeover relay can be displayed via
the Service level.
Main menu > Heating/cooling changeover
Operating line
Heating/cooling changeover relay
In a 2-pipe heating/cooling system without a "Heating/Cooling changeover" signal
on the KNX bus, the controller continues to use the last received value. If the signal
never existed, then "Heating" is used as the default value.
No.
Text
5801
H/C changeover
signal failure
If the "H/C changeover" in a 2-pipe system is configured so that it is initiated by
calendar or by operating mode selector, and a changeover signal is received in one
of the zones from another device, then the fault message "> 1 heat/cool
changeover signal" is transmitted.
No.
Text
5802
>1 heat/cool
changeover signal
Basic documentation: Communication via the KNX bus
Appendix
Range
No, Yes
Range
01.01. - 31.12.
01.01. - 31.12.
Range
----, N.Q1, N.Q2,.../
Current contact position (status)
Open (Off) Cooling / Closed (On) Heating
Effect
Non-urgent message; no acknowledgement
required.
Effect
Non-urgent message; acknowledgement is
required.
Factory setting
No
Factory setting
01.10.
01.05.
Factory setting
----
99/120
CE1P3127en
30.08.2007