Qawz740 Room Unit - Siemens Synco 700 Series Basic Documentation

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Step 4
RM...controllers
RM...B controllers
Zone addresses
in networks
Setting procedure
Note
Building Technologies
HVAC Products
Press the knob to confirm the zone address just set.
Room
Geogr. zone (ap.):
Time switch op:
TS slave (apart.):
Room
Geogr. zone (ap.):
TS slave (apart.):
Time switch op:
Geographical zone (apartment), RM... controllers
RM... default
1
RM... B default
----
Settings
1...126
In extensive networks it is more efficient to set zone addresses via ACS Service
than to use the RMZ790 and RMZ791 operator units (see section 5.1).
7.2.2

QAWZ740 room unit

The QAW740 room unit only contains the "Geographical zone (apartment)". The
zone address can be set by use of the operator controls on the front of the unit.
Step
Action
1
For access to the setting mode, press the presence
button for approximately 6 seconds. A letter A is
displayed and the zone address can be set.
2
Set the zone address with the rotary knob,
In this example, the value is 5, hence A 5
Note: A stands for "Geographical zone (Apartment)"
3
Briefly pressing the presence button again takes the
user to other settings (for setting values with rotary
knob, see Step 2).
After setting the zone address, press the presence
4
button to exit from setting mode.
Zone address in the range 1...126 can be set for the "Geographical zone
(apartment)" in the QAW740 room unit.
Basic documentation: Communication via the KNX bus
Communication via zone addresses
5
Autonom
1
5
----
Autonom
Operator
controls
73/120
CE1P3127en
30.08.2007