Siemens Synco 700 Series Basic Documentation page 52

Communication via the knx bus
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Assigning addresses
manually
Programming mode
Bus power
52/120
Building Technologies
HVAC Products
1. In ACS Service select Plant > Edit device list... to open the "Edit device list" dialog
box (see section 5.2.1).
2. Select the room unit with the left mouse button and click the button
Manually...
marked
to open the "Address assignment" dialog box.
3. Enter a device address in the range 1...253 (excluding 150), and confirm by
Write
clicking the
button.
1. Set the room unit locally to programming mode. To do this, press the presence
button for approximately 12 seconds. The display reads Prog.
2. In ACS Service select Plant > Edit device list... to open the "Edit device list" dialog
box (see section 5.2.3). Click the
assignment" dialog box.
3. Enter a device address in the range 1...253 (excluding 150), and confirm by
clicking the
Write
button.
When the new device address has been adopted, the room unit reverts to a
display of the room temperature.
The room unit only switches to programming mode if the bus power is available.
Basic documentation: Communication via the KNX bus
Device addresses via ACS
Programming mode...
button to open the "Address
CE1P3127en
30.08.2007