Error
Diagnostic
Device
code
code
59
#
BU
59
#
BU
5A
#
BU
5A
#
BU
5B
#
BU
5B
#
BU
5C
#
BU
5C
#
BU
206/278
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
15 Addendum 1: List of fault status messages of LMV51... system
Display
Parameter Set damaged
After initialization, EEPROM page is on
ABORT (last parameterization was
possibly interrupted due to a power
failure)
Parameter Set damaged
Page number
Parameter Set damaged
CRC error of a parameter page
Parameter Set damaged
Page number
Parameter Set damaged
Page is on ABORT
Parameter Set damaged
Page number
Parameter Backup Restore
Page is on WR_RESTO
A backup restore was made
Parameter Backup Restore
Page number
Meaning for the LMV5x system
Troubleshooting
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit.
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit
Reset the unit.
! Caution ! If fault occurred during parameterization: Check
the parameters changed last.
If fault cannot be rectified by the reset: Restore AZL...
parameters.
Otherwise, replace defective basic unit
Reset the unit.
CC1P7550en
01.10.2003