Siemens LMV5 Series Basic Documentation page 127

Burner control with integrated fuel / air ratio control, burner control with load control and oxygen trim control for forced-draft burners
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Parameterdarstellung auf Basis der Menüstruktur AZL - Ebene «OEM» - Auslieferstand Siemens Landis&Staefa
Menu level 1
Menu level 2
Menu level 3
Siemens Building Technologies
Basic Documentation LMV51...
HVAC Products
7 Display and operating unit AZL5...
Menu level 4
Menu level 5
Menu level 6
HomePos
HomePosGas
HomePosAir
HomePosAux
HomePosAux2
HomePosAux3
HomePosVSD
PrepurgePos
PrepurgePosAir Prepurge position of air damper (gas)
PrepurgePosAux Prepurge position of auxiliary damper (gas)
PrepurgePosAux
2
PrepurgePosAux
3
PrepurgePosVS
D
IgnitionPos
IgnitionPosGas
IgnitionPosAir
IgnitionPosAux
IgnitionPosAux2 Ignition position of auxiliary damper 2
IgnitionPosAux3 Ignition position of auxiliary damper 3
IgnitionPosVSD
PostpurgePos
PostpurgePosGa
s
PostpurgePosAir Postpurge position of air damper (gas)
PostpurgePosAu
x
Description
Setting the home positions for firing on gas
Home position of fuel damper (gas)
Home position of air damper (gas)
Home position of auxiliary damper (gas)
Home position of auxiliary damper 2
Home position of auxiliary damper 3
Home position of VSD
Setting the prepurge positions for firing on gas
Prepurge position of auxiliary damper 2
Prepurge position of auxiliary damper 3
Prepurge position of VSD
Setting the ignition positions for firing on gas
Ignition position of fuel damper (gas)
Ignition position of air damper (gas)
Ignition position of auxiliary damper (gas)
Ignition position of VSD
Setting the postpurge positions for firing on gas
Postpurge position of fuel damper (gas)
Postpurge position of auxiliary damper (gas)
Value range
Access
Default
LMV51 LMV52
rights
parameter
setting
Service
x
0..90°
Service
x
0..90°
Service
x
0..90°
Service
x
0..100%
0..90°
Service
0..90°
Service
0..100%
Service
Service
x
0..90°
Service
90°
x
0..90°
Service
90°
x
0..100%
0..90°
Service
90°
0..90°
Service
90°
0..100%
Service
100%
Service
x
0..90°
Service
invalid
x
0..90°
Service
invalid
x
0..90°
Service
invalid
x
0..100%
0..90°
Service
invalid
0..90°
Service
invalid
10..100%
Service
invalid
Service
x
0..90°
Service
15°
x
0..90°
Service
15°
x
0..90°
Service
25°
x
0..100%
CC1P7550en
01.10.2003
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
127/278

Hide quick links: