24. Ignition positions
Menu level 1
Menu level 2
Params & Display
RatioControl
158/278
Siemens Building Technologies
HVAC Products
The burner control proceeds with the startup sequence until the ignition position (Phase
36) is reached. There, the burner control stops again for setting the ignition positions of
the actuators.
Menu level 3
OilSettings
To repeatedly verify the ignition positions, the program sequence can be stopped in
interval phase 44 or 52 (interval with ignited flame on completion of the respective
safety time).
When the program stop is deactivated, the burner proceeds with its program until normal
operation is reached (Phase 60).
If the switching points of the burner stages have not yet been defined, the ignition
positions of the actuators will be used as the first stage for the moment.
Basic Documentation LMV51...
8 Commissioning instructions for the LMV5... system
Menu level 4
Menu level 5
SpecialPositions
IgnitionPos
Menu level 6
IgnitionPosOil
IgnitionPosAir
IgnitionPosAux
Aux2
Only
Aux3
LMV52...
VSD
CC1P7550en
01.10.2003