4.7.5.5
Technical data
Table 4- 19
Technical data of the external fan unit
6SL3161-0EP00-0AA0
Input voltage
Power consumption
Electronics current drawn at 24 V DC
Volumetric rate of air flow
Service life
Dimensions (W x H x D)
Weight
Degree of protection
4.8
Electrical connection
4.8.1
Stripped length for the line supply and power cables
Non-prefabricated MOTION-CONNECT power cables must be appropriately prepared before
being connected to the S120 Combi.
Note
Special issue for UL applications
For UL applications, use 60/75° C copper cables.
Cables without connection cables for the motor holding brake
1. Cut the cable jacket to dimension A from the table below
2. Strip the single cores U, V, W and protective conductor, and crimp on end sleeves with
insulation support (according to DIN 46228-E)
Cables with connection cables for the motor holding brake
1. Cut the cable jacket to 250
2. Cut the single cores U, V, W and protective conductor to dimension A from the table
below, strip and crimp on end sleeves with insulation support (according to DIN 46228-E)
3. Strip the connection cables for the motor holding brake and screw to the brake connector
SINAMICS S120 Combi
Manual, 11/2017, 6SL3097-4AV00-0BP7
Unit
V
DC
W
A
m
/h
3
h
mm
kg
mm
± 5
S120 Combi Power Modules
4.8 Electrical connection
Value
20.4 ... 28.8
18
0.8
290
50000 at 55 °C
258 x 104 x 86
1.5
IP54
103