Westerm D20M++: Power Supply; Peripherals: Supplying Power - GE D20 Installation And Operation Manual

Hide thumbs Also See for D20:
Table of Contents

Advertisement

D20/D200
Installation and Operations Guide
Connections and Configuration
WESTERM
Power Supply connections on the WESTERM D20M++:
D20M++:
Power Supply
1 & 2 are used for input power connections based upon the WESDAC D20
Power Supply
Peripherals:
Power supply to the WESDAC/WESTERM peripheral pairings is through the
Supplying
WESTERM boards.
Power
If you have the D20 horizontal slot chassis for a VME or non-VME installation, then
power supply to the I/O Peripherals can be run through the D.20 Link. This is also
possible for a D20 two-node implementation of this chassis assembly. If you have
the D200 vertical slot chassis for multi-node, then you cannot run the power supply
to the I/O Peripherals through the D.20 Link; you require the D.20 DC Interface
module: See "D.20 Interface Modules: connect for power using D.20 Link", page 61
In RTU systems using more that five peripherals, an external power supply is
required and this supply is wired directly onto the WESTERM board. Typical power
consumption for D20 I/O peripherals is as follows:
54
, continued
D20A
20 – 60 VDC, 8 W typical
D20C
20 – 60 VDC, 5 W typical
D20K
20 – 60 VDC, 4 W typical, 11 W
with all relays energized
D20S
20 – 60 VDC, 3 W typical
994-0078-2.00-7