D20/D200 Software Configuration
Procedure (continued)
Step
Optional Step 2: Provide feedback during download
10
Download Code File
11
12
13
14
General
Full
, continued
If the communication software you are using does not have any
"progress indicator", then echo can be enabled to visually display the
code file on your monitor as it is transferred.
This option can be usually found in the communication settings or
properties of the communication program.
Note:
Enabling echo may slow transfer slightly.
Press
to verify that communication is active.
ENTER
Result:
The D20M> prompt will return, if connection is active.
Type dl and press
ENTER
ready to receive the downloadable code file.
Click Transfer | Send Text File from menu bar.
Result:
A dialog box will open, prompting you to locate the Down.shx
file that you wish to download.
Select the correct file, and click Open to start the transfer.
Caution: Do not hit any keys on keyboard during download.
Result:
The file transfer may take from less than 10 to over 30
minutes, depending on communication speed selected.
When complete, the D20M> prompt will return.
994-0078-2.00-7
Installation and Operations Guide
Action
to put the D20ME into the state where it is
D20/D200
103