D20/D200
Installation and Operations Guide
D20/D200 Software Configuration
Procedure (continued)
Step
Optional Step 1: Speed-up communications to shorten download time.
8
9
Optional Step 2: Provide feedback during download
10
Download Code File
11
12
13
14
106
, continued
Type Baud 38400 and press
Note:
Speeds up to 230.4 kbps, or lower speeds may be chosen based
on ambient EMI, WESMAINT cable length, PC and
communication software limitations, etc. Refer to "Appendix
B: 68K Monitor Commands", page 127 for supported speeds.
Result:
The monitor will now be communicating at 38.4 kbps
Configure the terminal emulator software to communicate at the same
speed, and reconnect to the 68K monitor.
If the communication software you are using does not have any
"progress indicator", echo can be enabled to visually display the code
file on your monitor as it is transferred.
This option can be usually found in the communication settings or
properties of the communication program.
Note:
Enabling echo may slow transfer slightly.
Press
to verify that communication is active.
ENTER
Result:
The D20MES> prompt will return if connection is active
Type dl and press
ENTER
ready to receive the downloadable code file
Click Transfer | Send Text File from menu bar
Result:
A dialog box will open, prompting you to locate the Down.shx
file that you wish to download.
Select the correct file, and click Open to start the transfer
Caution: Do not hit any keys on keyboard during download.
Result:
The file transfer may take from less than 10 to over 30
minutes, depending on communication speed selected.
When complete, the D20MES> prompt will return.
994-0078-2.00-7
Action
.
ENTER
to put the D20ME into the state where it is
GE Energy
Continued on next page