Panasonic EBL128 Planning Instructions page 89

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
Figure 16. The EBLWin dialog box "Interlocking Combination".
Logical Name:
Displayed in the EBLWin Tree and List views.
Default name can be changed when wanted / required.
Area and Point: Each "Interlocking Combination" is presented as
Area-Point (compare with Zone-Address). Area numbers 1-99 are
possible to use and Point numbers 1-99 are possible to use.
Available interlocking outputs list displays all the previous
programmed outputs, Type = "Interlocking Output".
Available interlocking inputs list displays all the previous
programmed inputs with the Triggered by alternative (trigger
condition) 10 = "Interlocking Input".
Select one output and one input in the list respectively.
and the selected output and input will be shown in the Selected
output and Selected input field respectively.
Text = Interlocking text to be shown in the menu H9/C1. Can be
written in this field or in the "Texts" dialog box, see chapter "Creating
the alarm texts via EBLWin", page 114.
Buzzer checked = activated interlocking input will turn on the
EBL128 buzzer (0.8 / 0.8 sec.)
be automatically turned on again, if a new interlocking input is
activated.
Latched output checked = Output reset has to be performed via menu
H9/C3. (Automatically output reset will not take place when the
control expression becomes false.).
Fault checked = Fault detection ON.
90
Output / Input parent will then show in which unit the output / input
respectively is situated.
91
Priority order: Fire alarm – Pre-warning - Interlocking - Fault.
EBL128 Planning Instructions V2.0.x
91
. The buzzer can be silenced. It will
87
90
Press Select