Panasonic EBL128 Planning Instructions page 67

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
1. Activated input will activate an output (Technical address /
output.)
2. "Activated Fault routing equipment" signal (feed-back) to
EBL128 will light up the LED "Fault tx activated" on the front.
Output with trigger condition "Indication Fault tx Activated" will
be activated.
3. Activated Ventilation equipment feedback to the EBL128 control
unit to light up the LED "Ventilation".
4. Output with trigger condition "Activated Key cabinet" will be
activated.
5. "Activated Fire brigade tx" signal (feed-back) to EBL128 will
light up the LED "Fire brigade tx" on the front. (Normally the
LED will be lit when a corresponding output is activated
Output with trigger condition "Indication Fire Brigade tx
Activated" will be activated.
6. Key cabinet, where the fire brigade store a key to the building.
Will activate a Key cabinet alarm. See the EBL128 Operating
Instructions for more information.
7. Alert annunciation, see the EBL128 Operating Instructions for
more information.
8. Like 7.
9. "Fire door closing" outputs will be activated for 20 seconds by
this trigger condition.
10. Activated input will activate all programmable outputs of type
"Alarm devices" steady (continuous).
11. Ext. fault will activate a fault in EBL128. A user definable fault
message ("text") with up to 40 characters will be shown.
12. External clock, timer, key switch, switch, etc. can disable / re-
enable alarm points. The function Alert annunciation can be set
on / off by a time channel. Control outputs can be turned on
(activated) / off (de-activated) by a time channel.
13. Activated input will activate a fire alarm in EBL128 (Zone no.)
from an extinguishing system.
14. Used to start a new "countdown", see 15 below.
Push button: NO, momentary action. One or more push buttons
can be used.
15. Output for Extinguishing equipment (type of output = 2) has to
have a delayed activation programmed (a "countdown"). This
"countdown" will be stopped when an input with trigger condition
15 is activated. To start a new "countdown", see 14 above.
Push button info: NO, latching action. One or more push buttons
can be used. Manual reset of push button(s).
65
Type of output = Routing equipment (Fire brigade tx).
EBL128 Planning Instructions V2.0.x
65
65
.)

Hide quick links: