Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Eco Solutions Nordic AB
MEW01622
Rev: -
6.1.5.1
6.1.5.2
6.1.5.3
6.1.5.4
Intrinsically Safe (IS) mounting bases
YBN-R / 4 IS
Intrinsically Safe mounting base (2812). In the
base can be plugged a conventional intrinsically safe smoke
(2810) or heat (2811) detector. The base has terminals for the
zone line (in/out) and for an ext. LED.
connected to a Galvanic isolator (2820)
Intrinsically Safe photoelectric smoke detectors
SLR-E-IS Intrinsically Safe photoelectric smoke detector (2810).
A conventional intrinsically safe photoelectric (optical) smoke
detector, shall be plugged in the intrinsically safe mounting base
(2812). The detector has two built-in LEDs that are lit to
indicate that the detector has generated fire alarm.
classification: Cat. 1, 2 or 3. BASEEFA / ATEX classification:
EEx ia IIC T5, T
amb
2840 Analog IS smoke detector.
electric smoke detector. The detector can be used with a back-
box 2843 for higher IP rating. Three cable glands are supplied
with the back-box.
indicate that the detector has generated fire alarm. The detector
is in EBLWin programmed as an analog photoelectric smoke
detector 4401 (in NORMAL mode) but it has to be connected to
a COM loop via an IS barrier unit 2842. DEKRA: Ex II 1 G Ex
ia IIC T5 Ga. (2842 and 2843 have to be ordered separately.)
Intrinsically Safe heat detectors
DCD-1E-IS Intrinsically Safe heat detector (2811). A conventional
intrinsically safe Rate of Rise heat detector, fixed temperature
60°C (class A1), shall be plugged in the intrinsically safe
mounting base (2812).
indicate that the detector has generated fire alarm.
classification:
classification: II 1 G EEx ia IIC T5, T
per zone.
2841 Analog IS heat detector. An analog / addressable heat detector.
The detector can be used with a back-box 2843 for higher IP
rating. Three cable glands are supplied with the back-box. The
detector has one built-in LED to indicate that the detector has
generated fire alarm. The detector is in EBLWin programmed
as an analog heat detector 3308 (in NORMAL mode) but it has
to be connected to a COM loop via an IS barrier unit 2842.
DEKRA: Ex II 1 G Ex ia IIC T5 Ga. (2842 and 2843 have to
be ordered separately.)
Intrinsically Safe manual call points
MCP 1A-R470SGIS
A conventional outdoor manual call point (NO contact and
alarm resistor 470 ohms). The call point is connected to a
EBL128 Planning Instructions V2.0.x
= 50°C. Max 20 per zone.
An analog / addressable photo-
The detector has one built-in LED to
Two built-in LEDs that are lit to
Cat. 1,
2 or 3.
= -20 to +55°C. Max 20
a
Intrinsically Safe manual call point (2814).
51
The zone line is
Zone
Zone
BASEEFA / ATEX