Fan control panel 4593 has two Fan control application boards 4594
and two Fan control fronts. See Technical Description Fan control
panel 4593 (MEW01245).
Each Fan (0-3) (i.e. each Fan control) has to be added and
programmed via EBLWin.
For each fan, also one I/O unit 3361 is required. It has to be added in
EBLWin as an I/O unit for fan control 3361 and programmed
regarding e.g:
Technical address (COM loop address 1-255)
Name (Fan control I/O unit - normally not changed)
Fan control information
 I/O Matrix fan control (Fan control / fan 0-3)
 Supervised or not supervised (Input In0)
 Output latched or not latched
 Enhanced fan control function or not.
 Fault detection time (Input In0; 30-255 seconds)
Properties (for Re0)
Normally stopped or Normally running

Zone control

Used for application board type Zone control.
Each input (0-15) has to be programmed via EBLWin regarding:
Zone (control) no. (0-15)
29
If Re0 is normally open, Re1 will automatically be normally closed and
vice verse. If "Enhanced fan control function" is selected an Re1 tab will be
available for individual programming of Re1.
EBL128 Planning Instructions V2.0.x
29
29
, like any programmable output.