Installing End Caps; Fastening The Pipe System - Siemens FDA241 Planning, Mounting

Asd pipe system
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

5.2.3 Installing end caps

5.2.4 Fastening the pipe system

Building Technologies
Fire Safety
Glue an end cap on to each open end of the pipe system as described in chapter
'Connecting pipes and fittings [
An aspirating hole must be created in each end cap. The aspirating holes in the
end caps usually have a larger diameter than the aspirating holes in the pipes. As
a result of the end cap, an initial airflow is generated in the pipe system.
Exception: The end caps on the upright stand pipes do not have any aspirating
holes in them.
See also
End caps [
Drilling the aspirating holes [
The pipe system can be secured in various ways. Please refer to the following
chapters:
Fastening on the ceiling
See chapter: Installing pipes on the ceiling (standard) [
Fastening under the floor
See chapter: Installing pipes in false floors or channels [
Installing upright stand pipes
See chapter: Installing upright stand pipes [
Installing capillary tubes
See chapter: Air aspiration via capillary tubes [
The basics of fastening
We recommend using fastening clamps, which can be installed on the wall or
ceiling. The pipes are hung in the fastening clamps.
Observe the following points when fastening the pipe system:
The exact installation procedure depends on the fastening clamps used and
the available substructure. Use suitable dowels and screws.
Pipes may expand due to fluctuations in temperature. Ensure that there is
sufficient space for the pipes, e.g. to the side of the pipes.
Ensure that there are no fastening clamps near the aspirating holes.
Do not install any fastening clamps within an area of approx. 1000 mm in front
of the aspirating smoke detector. This simplifies the process of removing the
pipe system from the aspirating smoke detector for maintenance and cleaning.
See also
Fastenings [
Mounting/Installation
Installing the pipe system
50]'.
28]
52]
43]
45]
20]
29]
5