Application of standards for conventional detectors

4.6 Application of standards for conventional detectors
34 | 56
Building Technologies
Fire Safety
Each aspirating hole corresponds to a smoke detector position. Prior to planning
and installation, check whether the applicable standards have been sufficiently
taken into account. When planning the pipe network, consider how the air moves in
the room and the detection area covered by the aspirating holes. Each aspirating
hole can monitor an area of between 10 m² and 60 m².
5 m
Figure 7: Example detection network with a mesh size of 5 m
A6V10334435_g_en_--
2017-09-12