Installing Pipes On The Ceiling (Standard) - Siemens FDA241 Planning, Mounting

Asd pipe system
Hide thumbs Also See for FDA241:
Table of Contents

Advertisement

4.13 Installing pipes on the ceiling (standard)

Building Technologies
Fire Safety
For the pipe system, use the Components of the pipe system [
The pipes are secured under the ceiling using plastic brackets.
The correct distance between the pipe and the ceiling is 25...100 mm.
The maximum distance (a) between two retaining points is 200 cm. In locations
that are subject to strong vibrations and very severe fluctuations in
temperature, the maximum distance between two retaining points is 30 cm.
The mounting components used must allow the pipe to expand freely in the
event of temperature changes.
The mounting components must be placed a considerable distance away from
the aspirating holes in the pipe to prevent the aspirating holes from being
covered up when the length of the pipe changes due to a change in
temperature.
Pipes can also be secured to components using equipment such as cable ties.
1
Cable tie
2
Pipe
Installing pipes on the ceiling (standard)
a
1
a
Planning
4
27].
25 - 100 mm
1
2
43 | 56
A6V10334435_g_en_--
2017-09-12