Technical specifications of POM4320 rear panel mounting (-0AA2)
Article number
General information
Product type designation
Installation type/mounting
Mounting type
Mounting position
Type of ventilation
Supply voltage
Type of supply voltage
Rated value (AC)
Relative negative tolerance
Relative positive tolerance
2nd rated value (AC)
Relative negative tolerance
Relative positive tolerance
Line frequency
•
•
•
Mains buffering
•
Connection method
•
Input voltage
Design of the power supply
Power
Active power input, max.
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
Rated value 50 Hz
Rated value 60 Hz
Relative symmetrical tolerance
Recovery time after power failure,
typ.
Design of electrical connection for
supply voltage
–
Connectable conductor cross-
sections, solid
–
Connectable conductor cross-
sections, finely stranded with
wire end processing
–
Connectable conductor cross-
sections for AWG cables
13.2 Technical Specifications POM4320
6BK1943-2CA00-0AA2
POM4320 rear panel
mounting (IEC)
Backplane mounting
vertical
Self-ventilation
AC
400 V
10 %
30 %
480 V
25 %
8 %
Yes
Yes
5 %
1 s
Terminal, 3-pin
1x (1.5 ... 50 mm²)
1x (1.5 ... 35 mm²)
1x (16 ... 1)
Power supply via CIM
8 W
Technical specifications
6BK1943-2DA00-0AA2
POM4320 rear panel
mounting (UL)