Vau 01.1Z - Connecting The 115/230 Vac Voltage Supply - Bosch Rexroth IndraControl VAU 01.1 Series Operating Instructions Manual

With communication interface
Table of Contents

Advertisement

Bosch Rexroth AG
Assembly, Disassembly and Electrical Installation
Connection
Power supply unit and UPS
UPS and PC ②
①, ② see
fig. 10-4 "Wiring of the UPS" on page 23
Tab. 10-3: Cable lengths and cross-sections if the load changes
VAU 01.1Z
Cable length ①
1 m to 7 m
8 m to 9 m
10 m
see
fig. 10-4 "Wiring of the UPS" on page 23
Tab. 10-4: Required cable cross-sections for the DC 24 V voltage supply depending on the
cable length when wired firmly
The following data applies if the load changes immediately caused by connect-
ing or disconnecting loads (not wired firmly) at the UPS:
Connection
Power supply unit and UPS
UPS and PC ②
①, ② see
fig. 10-4 "Wiring of the UPS" on page 23
Tab. 10-5: Cable lengths and cross-sections if the load changes
10.5.2 VAU 01.1Z – Connecting the 115/230 VAC Voltage Supply
The VAU 01.1Z UPS features an integrated power supply unit, which provides
the buffer voltage for the PC, instead of a battery.
Connection
1. Connect X1N1 to the 115/230 VAC connection of the main UPS as shown
in the following figure.
24/53
Length
Maximum 2 m
Maximum 2 m
Cross-sections when wired firmly
1.0 mm
2
(AWG17)
1.5 mm
2
(AWG15)
2
2.5 mm
(AWG13)
Length
Maximum 2 m
Maximum 2 m
Cross-section
2
Min. 5.0 mm
(AWG10)
Min. 2.5 mm
2
(AWG13)
Cross-section
Min. 5.0 mm
2
(AWG10)
Min. 2.5 mm
2
(AWG13)
DOK-SUPPL*-VAU*01.1X**-IT02-EN-P
VAU 01.1