VAU 01.1
Output voltage
Nominal output voltage
Output voltage range
Current output at U
N
Switching time
Bridging time
Max. output power
Short-circuit protection
Tab. 7-4: Output voltage 24 V
NOTICE
The max. power consumption of the connected control cabinet PC or panel PC
must not exceed the max. output power of the UPS of 240 W.

7.2 VAU 01.1Z

7.2.1 Degree of Protection and Weight

Enclosure rating
Weight
Tab. 7-5: Degree of protection and weight
DOK-SUPPL*-VAU*01.1X**-IT02-EN-P
DC 24 V (use a 24 V power supply unit according
to DIN EN 60742, classification VDE 0551, for ex-
ample the power supply unit VAP01.1H-
W23-024-010-NN, part number R911171065)
DC 24 V +20 %, -15 %
Maximum 10 A
< 1 ms
3 minutes max.
240 W
VAU 01.1S: No
VAU 01.1U (from technical index GC1): Yes
Note:
A short circuit in the UPS VAU 01.1U results in an
immediate switch-off of the output voltage. A new
switch on can only take place after switching
off/on of the input voltage. To load capacitive
loads, a cut-out delay of 300 ms during the start-
ing operation is incorporated. This results in a
maximum permissible capacitive load of 5600 μF
at 5 A resistive load during the starting operation
Overheating and possible damage to the UPS if
the max. power consumption is exceeded.
IP 20
1 kg
Bosch Rexroth AG
Technical Data
11/53