Line Modules
4.2 Basic Line Modules
4.2.3.3

Line/load connection

Table 4- 2
Line/load connection of the Basic Line Module
Terminals
U1, V1, W1
3 AC power input
DCP, DCN
DC power output
PE connection
4.2.3.4

X9 terminal strip

Table 4- 3
Terminal strip X9
Terminal
1
1
2
2
3
4
5
6
7
8
Max. connectable cross-section 1.5 mm
Note
For operation, 24 V DC must be connected to terminal 7 and ground to terminal 8. Pulse
suppression is activated when terminals are disconnected.
Note
The two "P24 V" or "M" terminals are jumpered in the connector. This ensures that the
supply voltage is looped through, even when the connector is removed.
90
Technical specifications
Voltage:
3 AC 380 V -10 % (-15 % < 1 min) to 3 AC 480 V +10 %
3 AC 500 V -10 % (-15 % < 1 min) to 3 AC 690 V +10 %
Frequency: 47 Hz to 63 Hz
Connecting thread: M12/50 Nm for busbar connection
Voltage:
513 V to 648 V DC
675 to 932 VDC
Connecting thread: M12/50 Nm for busbar connection
Connecting thread: M12/50 Nm for busbar connection
Signal name
P24 V
P24 V
M
M
Reserved, do not use
Main contactor control
EP +24 V (Enable Pulses)
EP M1 (Enable Pulses)
2
Technical specifications
Voltage: 24 V DC (20.4 V – 28.8 V)
Power consumption: See Technical data
240 V AC: max. 8 A
30 V DC: max. 1 A
isolated
Supply voltage: 24 V DC (20.4 V - 28.8 V)
Power consumption: 10 mA
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
Chassis Liquid Cooled Power Units